PROCON-WEB Embedded Systems 6.11.2¶
Warning
The system can therefore be accessed at https://localhost:17443.
Access via the old port is no longer possible.
Fixes & improvements¶
126062: Fixed an issue that prevented messages from switching languages at runtime.
Known issues¶
Firmware bug in Siemens 1500 series CPUs running firmware 4.x: Frequent connection and disconnection with the PLC visible in the event log. A fix via a firmware update from v4.0.4 onwards improves the situation, but does not resolve the problem completely. A solution is expected to be released with firmware 4.2 in December 2026. Further information in the Siemens Release Notes. TIA drivers are therefore not currently approved for firmware v4.x.
The TIA V2 driver does not currently support importing fields from structures. Instead, the driver creates an element for each index.
The setup for Windows systems does not create a port share, which is why streaming does not work. Port 17443 must be manually enabled in the Windows Defender Firewall in the incoming rules under Windows.